DN-7087:C1 • 11/9/11 — Page 1 of 4
SpectrAlert
®
Advance
Selectable Output
Notification Appliances
Audio/Visual Devices
DN-7087:C1
General
System Sensor® SpectrAlert® Advance selectable-output
horns, strobes and horn/strobes are rich with features guaran-
teed to cut installation times and maximize profits. The Spec-
trAlert Advance series of notification appliances is designed to
simplify your installations, with features such as: plug-in
designs, instant feedback messages to ensure correct installa-
tion of individual devices, and eleven field-selectable candela
settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first
attach a universal mounting plate to a four-inch square, four-
inch octagon, or double-gang junction box. The two-wire
mounting plate attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate.
Finally, attach the horn, strobe, or horn/strobe to the mounting
plate by inserting the product’s tabs in the mounting plate’s
grooves. The device will rotate into position, locking the prod-
uct’s pins into the mounting plate’s terminals. The device will
temporarily hold in place with a catch until it is secured with a
captured mounting screw.
SpectrAlert Advance products allow you to choose:
12 or 24 volts.
15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or 185 can-
dela by way of a rear-mounted slide switch and front view-
ing window.
Horn tones and volume by way of a rotary switch.
The SpectrAlert Advance series includes outdoor notifica-
tion appliances. Outdoor strobes and horn/strobes (two-
wire and four-wire) are available for wall or ceiling. Outdoor
horns are available for wall only. All System Sensor outdoor
products are rated between –40°F and 151°F (–40°C and
66°C) in wet or dry applications.
Models available:
Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire
horn/strobe.
Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire
horn/strobe.
Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-
wire horn/strobe.
Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire
horn/strobe.
Features
Plug-in design.
Same mounting plate for wall- and ceiling-mount units.
Shorting spring on mounting plate for continuity check
before installation.
Captive mounting screw.
Tamper-resistance capability.
Field-selectable candela settings on wall and ceiling units:
15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.
Automatic selection of 12 or 24 volt operation at 15 and 15/
75 candela.
Outdoor wall and ceiling products.
Outdoor products rated from –40°F and 151°F (–40°C and
66°C).
Outdoor products rainproof per UL50 (NEMA 3R) and
weatherproof per NEMA 4X, IP56
Minimal intrusion into the backbox.
Horn rated at 88+ dbA at 16 volts.
Rotary switch for tone selection.
Three horn volume settings.
Electrically compatible with existing SpectrAlert products.
Engineering Specifications
SpectrAlert Advance horns, strobes, and horn/strobes shall
mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81
cm) backbox, 4.0" (10.16 cm) octagonal backbox, or a double-
gang backbox. Two-wire products shall also mount to a single-
gang 2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox. A
universal mounting plate shall be used for mounting ceiling
and wall products. The notification appliance circuit wiring
shall terminate at the universal mounting plate. Also, Spec-
trAlert Advance products, when used with the Sync•Circuit
Module accessory, shall be powered from a non-coded notifi-
cation appliance circuit output and shall operate on a nominal
12 or 24 volts. When used with the Sync•Circuit Module, 12-
volt rated notification appliance circuit outputs shall operate
between 9 and 17.5 volts; 24-volt rated notification appliance
circuit outputs shall operate between 17 and 33 volts. Indoor
SpectrAlert Advance products shall operate between 32°F and
120°F (0°C and 49°C) from a regulated DC, or full-wave-recti-
fied, unfiltered power supply. Strobes and horn/strobes shall
have field-selectable candela settings including 15, 15/75, 30,
75, 95, 110, 115, 135, 150, 177, 185.
Indoor Ceiling
Horn/Strobe
Outdoor Ceiling
Strobe
Indoor Wall
Horn/Strobe
Indoor Ceiling
Strobe
Indoor Wall
Horn
Outdoor Wall
Strobe
7087pho1.jpg
7087pho4.jpg
7087pho3.jpg
7087pho2.jpg
7087pho5.jpg
7087pho6.jpg
Vista de página 0
1 2 3 4

Resumo do Conteúdo

Página 1 - Advance

DN-7087:C1 • 11/9/11 — Page 1 of 4SpectrAlert® AdvanceSelectable Output Notification AppliancesAudio/Visual DevicesDN-7087:C1GeneralSystem Sensor® Spe

Página 2

Page 2 of 4 — DN-7087:C1 • 11/9/11STROBEThe strobe shall be a System Sensor SpectrAlert AdvanceModel _______ listed to UL 1971 and shall be approved f

Página 3 - STANDARD

DN-7087:C1 • 11/9/11 — Page 3 of 4Two-Wire Horn/Strobe, STANDARD Candela Range (15 – 115 cd),UL Maximum Current Draw (mA RMS)Input, Sound Pattern, dB

Página 4 - Ordering Information

Page 4 of 4 — DN-7087:C1 • 11/9/11Sync•Circuit™ is a trademark and NOTIFIER® and SpectrAlert® areregistered trademarks of Honeywell International Inc.