Notifier Field-Selectable Mass Notification Devices Manual do Utilizador Página 2

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 6
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 1
Page 2 of 6 — DN-60517:A • 06/02/2009
cans with Disabilities Act requirements for visible signaling
appliances, flashing at 1 Hz over the strobe’s entire operating
voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
HORN STROBE COMBINATION
The horn strobe shall be a System Sensor SpectrAlert
Advance Model _______ listed to UL 1971 and UL 464 and
shall be approved for fire protective service. The horn strobe
shall be wired as a primary-signaling notification appliance
and comply with the Americans with Disabilities Act require-
ments for visible signaling appliances, flashing at 1 Hz over
the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflec-
tor system. The horn shall have three audibility options and
an option to switch between a temporal three-pattern and a
non-temporal (continuous) pattern. These options shall be
set by a multiple position switch. The horn and horn strobe
models shall operate on a coded or non-coded power supply.
SPEAKER STROBE COMBINATION
The speaker strobe shall be a System Sensor SpectrAlert
Advance Model __________ listed to UL 1480 and UL 1971
and be approved for fire protective signaling systems.
Speaker shall be capable of operating at 25.0 or 70.7 nomi-
nal Vrms selected via rotary switch, and shall have a fre-
quency range of 400 to 4000 Hz. Speaker shall have power
taps that are selected by rotary switch. The strobe shall com-
ply with the NFPA 72 requirements for visible signaling appli-
ances, flashing at 1 Hz over the strobe’s entire operating
voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
OUTDOOR PRODUCTS
SpectrAlert Advance outdoor strobes, horn strobes and
speaker strobes shall be listed for outdoor use by UL and
shall operate between –40°F and 151°F (–40°C and 66°C).
The products shall be listed for use with a System Sensor
outdoor/weatherproof back box with half-inch and three-
fourths-inch conduit entries.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit model
MDL3R or MDL3W listed to UL 464 and shall be approved for
fire protective service. The module shall synchronize Spec-
trAlert strobes at 1 Hz and horns at temporal three. Also,
while operating the strobes, the module shall silence the
horns on horn strobe models over a single pair of wires. The
module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch (11.90
x 11.90 x 5.40 cm) back box. The module shall also control
two Style Y (class B) circuits or one Style Z (class A) circuit.
The module shall synchronize multiple zones. Daisy chaining
two or more synchronization modules together will synchro-
nize all the zones they control. The module shall not operate
on a coded power supply.
COLOR LENS STROBE ATTACHMENT
The System Sensor SpectrAlert Advance color lens attach-
ments shall be approved for fire protective service as listed in
UL 1638. The lens attachments shall only be used with (plain
non-fire-printed) System Sensor strobe devices. They shall
mount to any wall or ceiling strobe and be rated from –35°F
to 151°F (-37°C to 66°C).
Specifications
PHYSICAL SPECIFICATIONS
Standard Operating Temperature: 32°F to 120°F (0°C to
49°C)
K Series Operating Temperature: -40°F to 151°F (-40°C to
66°C)
Humidity Range: 10 to 93% non-condensing (indoor mod-
els)
Dimensions:
– Wall-Mount Strobe and Horn Strobe (including lens):
5.6” L x 4.7” W x 2.5” D
SPS Speaker Strobe (including lens and speaker):
6.0” L x 5.0” W x 4.7” D
Ceiling-Mount Strobe (including lens): 6.8” diameter
x 2.5” D
ELECTRICAL/OPERATING SPECIFICATIONS
Nominal Voltage (strobes and horn strobes): Regulated
12 DC/FWR or regulated 24 DC/FWR
Nominal Voltage (speakers): 25 V or 70.7 V (nominal)
Maximum Supervisory Voltage (speakers): 50 VDC
Operating Voltage Range: 8 to 17.5 V (12 V nominal) or 17
to 33 V (24 V nominal)
Strobe Flash Rate: 1 flash per second
Speaker Frequency Range: 400 to 4000 Hz
Speaker Power: ¼, ½, 1, 2 watts
SPEAKER SOUND OUTPUT
UL CURRENT DRAW DATA
UL Reverberant (dBA @ 10 ft.) 2W 1W 1/2W 1/4W
Wall-Mount SPS Series 85 82 79 76
Wall-Mount SPV Series 90 87 84 81
Ceiling-Mount SPC Series 86 83 80 77
Ceiling-Mount SPCV Series 90 87 84 81
UL Max. Strobe Current Draw (mA RMS)
8–17.5 Volts 16–33 Volts
Candela DC FWR DC FWR
Standard Can-
dela Range
15* 123 128 66 71
15/75* 142 148 77 81
30* NA NA 94 96
75* NA NA 158 153
95* NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High Candela
Range
135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258